Indexed by:
Abstract:
This paper presents a fluctuating voltage generation equipment for distributed generation grid-connected converter testing, which solves the challenge of testing distributed generation grid-connected converter in real power grid. The equipment is based on cascaded H-bridge structure, the voltage level of which is expandable. It can provide precise fluctuating voltage with fluctuating frequency ranging from 0.5 Hz to 25 Hz and fluctuating amplitude ranging from 0% to 10% of the fundamental voltage amplitude, and can simulate unbalance-degree-adjustable three-phase unbalance power grid, and the unbalance degree ranges from 0 to 10%. The equipment can fulfill voltage amplitude and frequency deviation, fluctuating voltage and grid unbalance adaptability test of the grid-connected converter. This paper analyzes the operating principle of this testing equipment and takes the field experimental result of the "35 kV-6MW wind turbine converter low-frequency disturbance testing equipment", which is based on the equipment topology proposed, as an example, sufficiently verifies the feasibility and effectiveness of utilizing this fluctuating voltage generation equipment for distributed generation grid-connected converter. ©, 2015, Chinese Machine Press. All right reserved.
Keyword:
Reprint Author's Address:
Email:
Source :
Diangong Jishu Xuebao/Transactions of China Electrotechnical Society
ISSN: 1000-6753
Year: 2015
Issue: 3
Volume: 30
Page: 115-122
Cited Count:
WoS CC Cited Count: 0
SCOPUS Cited Count:
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 10
Affiliated Colleges: