The internal equivalent impedance of DFIG may change during the system fault, which obviously impacts on the applicability of distance protection for the outgoing transmission line of wind farm. The power source characteristics and fault transient characteristics of DFIG-based wind farm are discussed and the action characteristics of phase-comparison distance protection based on polarized voltage are analyzed. The analytical results show the time-varying impedance circle characteristic may cause the improper action of distance protection during the system fault and the results of RTDS simulation prove the correctness of theoretical analysis. © 2016 Automation of Electric Power Systems Press.