Abstract:

This paper describes the experiment carried out to analyze the effects of improper refrigerant charge and incorrect TXV (Thermal Expansion Valve) opening on the air-source heat pump water heater using R134A. The performance of the system were measured in combinations of four refrigerant charges of 70%, 85%, 100% and 115% of the optimal value and three TXV opening of 30%, 45% and 60% of full opening at ambient temperature of 20D/15W (dry-bulb temperature/wet-bulb temperature). The results showed that the maximum COP was nearly 33%, 31.9% and 4.4% higher than that of 70%, 85% and 115% of the optimal refrigerant charge at 60% TXV opening, respectively. And it was found that the increase in TXV opening can enhance COP when water temperature exceeded 30°C. © 2015 Taylor & Francis Group, London.

Keyword:

Air source heat pumps Hot water distribution systems Pumps Refrigerants Solar water heaters Temperature Thermal expansion Water heaters

Author Community:

  • [ 1 ] [Wang, Zhi Hua]School of Energy and Power Engineering, Xi’an Jiaotong University, Xi’an; Shannxi, China

Reprint Author's Address:

  • [Wang, Zhi Hua]School of Energy and Power Engineering, Xi’an Jiaotong University, Xi’an; Shannxi, China;;

Email:

Show more details

Related Keywords:

Source :

Year: 2015

Page: 657-661

Language: English

Cited Count:

WoS CC Cited Count: 0

SCOPUS Cited Count:

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 7

FAQ| About| Online/Total:1177/160907416
Address:XI'AN JIAOTONG UNIVERSITY LIBRARY(No.28, Xianning West Road, Xi'an, Shaanxi Post Code:710049) Contact Us:029-82667865
Copyright:XI'AN JIAOTONG UNIVERSITY LIBRARY Technical Support:Beijing Aegean Software Co., Ltd.