Abstract:
This paper describes the experiment carried out to analyze the effects of improper refrigerant charge and incorrect TXV (Thermal Expansion Valve) opening on the air-source heat pump water heater using R134A. The performance of the system were measured in combinations of four refrigerant charges of 70%, 85%, 100% and 115% of the optimal value and three TXV opening of 30%, 45% and 60% of full opening at ambient temperature of 20D/15W (dry-bulb temperature/wet-bulb temperature). The results showed that the maximum COP was nearly 33%, 31.9% and 4.4% higher than that of 70%, 85% and 115% of the optimal refrigerant charge at 60% TXV opening, respectively. And it was found that the increase in TXV opening can enhance COP when water temperature exceeded 30°C. © 2015 Taylor & Francis Group, London.