Indexed by:
Abstract:
The fault ride-through (FRT) capacity has become an important grid requirement for fractional frequency offshore wind power system (FFOWPS) based on modular multilevel matrix converter (M3C). In this paper, a novel joint fault ride-through strategy is proposed, which employs a land grid voltage versus offshore grid frequency droop control on M3C. Then, the control system of wind turbines can adjust the generated active power from wind based on the offshore grid frequency. Different form the previous research, the proposed joint control method can maintain the stability of the M3C DC capacitor voltage under the premise of satisfying the reactive power support to the grid under fault condition. Simulation results validate the fault ride-through capability of the FFOWPS in MATLAB/Simulink. © 2019 IEEE.
Keyword:
Reprint Author's Address:
Email:
Source :
Year: 2019
Page: 716-719
Language: English
Cited Count:
WoS CC Cited Count: 0
SCOPUS Cited Count: 9
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 3
Affiliated Colleges: