Indexed by:
Abstract:
Partial discharge (PD) detection has proven to be one of the most acceptable techniques for on-line condition monitoring and predictive maintenance of power apparatus. A powerful tool for detecting PD in covered-conductor (CC) lines is urgently needed to improve the asset management of CC overhead distribution lines. In this paper, an appropriate, portable and simple system designed to detect PD activity in CC lines and ultimately pinpoint the PD source is developed and tested. The system is based on a novel double-side synchronised PD measurement technique driven by pulse injection. Emphasis is placed on the proposed PD-location mechanism and hardware structure, with descriptions of the pulse-injection process, detection device, synchronisation principle and PD-location algorithm. The system is simulated using ATP-EMTP, and the simulated results are found to be consistent with the actual simulation layout. For further validation, the capability of the system is tested in a high-voltage laboratory experiment using a 10-kV CC line with cross-linked polyethylene insulation.
Keyword:
Reprint Author's Address:
Email:
Source :
MEASUREMENT SCIENCE AND TECHNOLOGY
ISSN: 0957-0233
Year: 2015
Issue: 12
Volume: 26
1 . 4 9 2
JCR@2015
2 . 0 4 6
JCR@2020
ESI Discipline: ENGINEERING;
ESI HC Threshold:138
JCR Journal Grade:2
CAS Journal Grade:3
Cited Count:
WoS CC Cited Count: 3
SCOPUS Cited Count: 4
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 11
Affiliated Colleges: